Voltage Drop Calculator

Volts and watts a cable run loses, in AWG or mm². Physics only: it never sizes wire.

How many volts a cable run loses, for DC, single or three phase, copper or aluminium, in AWG, kcmil or mm², with the wire drawn to scale. Physics only: it does not size wire.

V
Common

From the supply to the load, not there and back.

Wire size
Conductor temperature75 °C (a warm conductor near full load)
°C
Common

Wire warms up under load: 20 °C cool and lightly loaded; 75 °C to 90 °C near full load.

ExampleVoltage drop

4.83%

100 ft of 12 AWG copper carrying 15 A on 120 V single phase loses 5.795 V, leaving 114.2 V at the load.

Enter your own run to see its drop.

0%3%5%10%
14 AWG7.7%13 AWG6.1%12 AWG4.8%11 AWG3.8%10 AWG3%Drawn to scale, with each size’s drop for this run
Volts lost
5.795 V of 120 V
Heat in the wire
86.92 W
Longest run for 3%
62.13 ft

Physics only: the drop for the size you picked, not a wire size for your circuit, which also depends on ampacity and your local code.

Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs. Terms

How this works: 6 sources,

How this works

Method

The drop is 2 × length × current × resistance per metre for DC and single phase, and √3 × length × current × resistance per metre between lines of a balanced three-phase circuit. Resistance per metre is the metal’s resistivity at its temperature (copper 1/58 Ω·mm²/m and aluminium 0.028264 at 20 °C, rising 0.393% and 0.403% per °C) over the cross-section; AWG areas come from the ASTM B258 diameter rule. Resistance only: reactance is left out, and nothing here sizes a wire.

How it’s tested

12 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.

Every change on What’s new

How we make toolsReport a mistake

Key facts

  • Annealed copper has a resistivity of 1/58 Ω·mm²/m (0.017241) at 20 °C, rising 0.393% per °C.
  • Each 3 AWG sizes halve the cross-section and double the resistance; 12 AWG is 3.31 mm².
  • 100 ft of 12 AWG copper carrying 15 A on 120 V loses about 5.8 V (4.8%) when warm at 75 °C.

Sources: NBS Handbook 100, Copper Wire Tables; ASTM B258

All 4 calculators

Voltage drop · Wire sizes and resistance

Where the volts go

Every wire is a long, thin resistor. The current through it makes a voltage across it, by Ohm’s law, so the load at the far end gets a little less than the supply. Twice the length or twice the current doubles the drop; twice the cross-section halves it. A circuit has two wires, out and back, so a single-phase or DC run of 30 m has 60 m of conductor in its loop.

The lost volts become heat in the cable: I² × R in every conductor. The card shows that heat in watts, which is energy you pay for and the cable has to shed. Lower voltages suffer most: losing 3 V is 2.5% of 120 V but 25% of 12 V, which is why low-voltage systems need short, thick runs.

This calculator uses resistance only. For large AC cables (roughly 50 mm² or 1/0 AWG and up) the cable’s reactance adds to the drop at power factors below 1; detailed design uses impedance tables for the actual cable, conduit and arrangement.

What this calculator does not do

  • It does not size a wire for a circuit. Ampacity (how much current a wire may carry) depends on insulation temperature rating, installation method, grouping and ambient temperature, set by the NEC, IEC 60364 or your national rules.
  • It does not check overcurrent protection, fault loop impedance or disconnection times.
  • It does not include terminal, breaker or connection resistance, which can add noticeably on low-voltage DC.

Sources

Common questions

How is voltage drop calculated?

From the wire’s resistance and the current: Vd = 2 × length × current × resistance per metre for DC and single phase (out and back), and √3 × length × current × resistance per metre for a balanced three-phase circuit. The resistance per metre is the metal’s resistivity at its temperature divided by the wire’s cross-section.

What is an acceptable voltage drop?

Common design targets are 3% for a branch circuit and 5% from the service to the furthest load: IEC 60364-5-52’s informative Annex G gives 3% for lighting and 5% for other uses, and the US NEC’s informational notes suggest similar figures. They are recommendations for performance, not limits on safety.

Does this tell me what wire size I need?

No, on purpose. A wire must carry its current without overheating, which depends on its insulation rating, how it is installed, bundling, ambient temperature and the rules where you are. Those ampacity rules are not here. Use this to check the voltage drop of a size you are considering, alongside your local code or an electrician.

Why does temperature matter?

Copper’s resistance rises 0.393% per °C and aluminium’s 0.403%. A conductor running warm at 75 °C has about 22% more resistance than at 20 °C, so it drops 22% more voltage. The calculator starts at 75 °C, a warm conductor near full load; pick 20 °C for a cool, lightly loaded run.

Copper or aluminium?

Aluminium has about 1.64 times copper’s resistance for the same cross-section, so it needs a larger size for the same drop. It is common for large feeders and service cables; it needs connectors and terminals rated for aluminium.