Watts to Amps Calculator
How much current a load draws from its power in watts.
How much current a load draws from its power in watts. Pick DC or AC, the voltage and, for motors and electronics, the power factor.
1 for heaters, kettles and lamps; often 0.7 to 0.9 for motors.
ExampleCurrent
12.5A
A 1,500 W load on a 120 V single-phase supply draws 12.5 A.
Enter your own values to see your result.
The dots speed up with more current; the load glows brighter with more power.
- Load resistance
- 9.6 Ω
- Energy in an hour
- 1.5 kWh
- At 240 V
- 6.25 A
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms
How this works: 8 sources,
How this works
Method
Power is voltage times current, so current is power divided by voltage. On a DC supply that is the whole formula: a 60 W fridge on a 12 V battery draws 60 ÷ 12 = 5 A. Halve the voltage and the same power needs twice the current, which is why low-voltage systems such as RVs, boats and solar setups use thick cables. Full method
Sources
- The International System of Units (SI Brochure), 9th edition (BIPM, 2019)
- University Physics Volume 2, §15.4 Power in an AC Circuit (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §9.4 Ohm’s Law (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §9.5 Electrical Energy and Power (OpenStax (Ling, Sanny and Moebs), 2016)
- IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities (IEEE, 2010)
- AC Electrical Circuit Analysis, §9.3 Three-Phase Connections (James M. Fiore, LibreTexts)
- AC Electrical Circuit Analysis, §9.4 Power Factor Correction (James M. Fiore, LibreTexts)
- IEC 60038:2009+AMD1:2021, IEC standard voltages (IEC, 2009)
How it’s tested
3 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.
How to convert watts to amps
Power is voltage times current, so current is power divided by voltage. On a DC supply that is the whole formula: a 60 W fridge on a 12 V battery draws 60 ÷ 12 = 5 A. Halve the voltage and the same power needs twice the current, which is why low-voltage systems such as RVs, boats and solar setups use thick cables.
AC adds the power factor. A heater, kettle or filament lamp is almost pure resistance, with a power factor of 1, so the DC formula still works: 1,500 W on 120 V is 12.5 A. A motor, compressor or cheap power supply draws some current that does no work, so its power factor is lower and it draws more amps for the same watts: 1,500 W at a power factor of 0.8 needs 1,500 ÷ (120 × 0.8) = 15.6 A.
On a three-phase supply the power is shared between three lines, so each line carries less: divide by √3 (about 1.732) times the voltage between lines. A 6 kW load on 400 V three phase draws 6,000 ÷ (1.732 × 400) = 8.7 A in each line, against 26 A on one 230 V phase.
DC: I = P ÷ V · AC single phase: I = P ÷ (V × PF) · three phase: I = P ÷ (√3 × V × PF)
- The watt is defined as one joule per second, and the volt as one watt per ampere, so watts ÷ volts gives amps exactly. Source: The International System of Units (SI Brochure), 9th edition.
- In an AC circuit the average power is P = I × V × cos φ, where cos φ is called the power factor. Source: University Physics Volume 2, §15.4 Power in an AC Circuit.
Watts to amps at common voltages
Current for each load at power factor 1 (heaters, kettles, filament lamps). Divide by the power factor for motors and electronics.
| Watts | 12 V DC | 120 V | 230 V | 240 V |
|---|---|---|---|---|
| 100 W | 8.33 A | 0.833 A | 0.435 A | 0.417 A |
| 250 W | 20.8 A | 2.08 A | 1.09 A | 1.04 A |
| 500 W | 41.7 A | 4.17 A | 2.17 A | 2.08 A |
| 750 W | 62.5 A | 6.25 A | 3.26 A | 3.13 A |
| 1,000 W | 83.3 A | 8.33 A | 4.35 A | 4.17 A |
| 1,200 W | 100 A | 10 A | 5.22 A | 5 A |
| 1,500 W | 125 A | 12.5 A | 6.52 A | 6.25 A |
| 1,800 W | 150 A | 15 A | 7.83 A | 7.5 A |
| 2,000 W | 167 A | 16.7 A | 8.7 A | 8.33 A |
| 2,500 W | 208 A | 20.8 A | 10.9 A | 10.4 A |
Show all 13 rowsShow fewer
| 3,000 W | 250 A | 25 A | 13 A | 12.5 A |
| 3,500 W | 292 A | 29.2 A | 15.2 A | 14.6 A |
| 5,000 W | 417 A | 41.7 A | 21.7 A | 20.8 A |
Common questions
How many amps is 1,500 watts?
12.5 A on a 120 V circuit, 6.52 A on 230 V and 6.25 A on 240 V, for a heater or kettle with a power factor of 1. On a 12 V battery through an inverter it would be 125 A before the inverter’s own losses.
Can I convert watts to amps without the voltage?
No. Watts are volts times amps, so the same power is a large current at a low voltage and a small one at a high voltage. Use the voltage on the appliance’s label, or your supply’s: 120 V in North America, 230 V in most of Europe, Asia and Africa, 240 V in the UK and Australia.
What power factor should I use?
Use 1 for anything that only heats: heaters, kettles, toasters, filament bulbs. Motors and compressors (fridges, pumps, air conditioners) are often 0.7 to 0.9 when running, and LED drivers and chargers vary widely; the label or datasheet may give it, or give the current directly.
Why does the label show more amps than this?
Labels often give the current at the lowest voltage the device accepts, or its start-up or peak current, which can be several times the running current for motors. The calculator gives the steady current for the power and voltage you enter.