kVA to Amps Calculator
The full-load current of a transformer or generator from its kVA rating and voltage.
The full-load current of a transformer or generator from its kVA rating and voltage. kVA counts all the current, whatever the power factor.
More optionsVoltage measured line to line; switch to line to neutral
ExampleCurrent per line
208.2A
A 75 kVA rating on a 208 V three-phase supply means up to 208.2 A in each line at full load.
Enter your own values to see your result.
Each line carries the same current, a third of a cycle apart.
- Real power at PF 0.8
- 60 kW
- Line to neutral
- 120.1 V
- At 400 V
- 108.3 A
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms
How this works: 8 sources,
How this works
Method
A kVA rating is the current a transformer or generator can deliver times its voltage, so the full-load current is the kVA divided by the voltage. For a 25 kVA single-phase transformer on 240 V that is 25,000 ÷ 240 = 104 A. No power factor comes into it: kVA already counts all the current, the part doing work and the part that isn’t. Full method
Sources
- IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities (IEEE, 2010)
- AC Electrical Circuit Analysis, §9.4 Power Factor Correction (James M. Fiore, LibreTexts)
- University Physics Volume 2, §9.4 Ohm’s Law (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §9.5 Electrical Energy and Power (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §15.4 Power in an AC Circuit (OpenStax (Ling, Sanny and Moebs), 2016)
- The International System of Units (SI Brochure), 9th edition (BIPM, 2019)
- AC Electrical Circuit Analysis, §9.3 Three-Phase Connections (James M. Fiore, LibreTexts)
- IEC 60038:2009+AMD1:2021, IEC standard voltages (IEC, 2009)
How it’s tested
2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.
How to work out amps from kVA
A kVA rating is the current a transformer or generator can deliver times its voltage, so the full-load current is the kVA divided by the voltage. For a 25 kVA single-phase transformer on 240 V that is 25,000 ÷ 240 = 104 A. No power factor comes into it: kVA already counts all the current, the part doing work and the part that isn’t.
For three phase, divide by √3 times the voltage between lines. A 75 kVA transformer at 208 V gives 75,000 ÷ (1.732 × 208) = 208 A per line; the same 75 kVA at 480 V is 90 A. That is why a building’s 480 V side has much smaller conductors than its 208 V side for the same kVA.
The real power a kVA rating can supply depends on the load. At a power factor of 0.8, which is the rating point for many generators, 75 kVA delivers 60 kW. That is why generator sets often show both: 100 kVA / 80 kW.
Single phase: I = 1,000 × kVA ÷ V · three phase: I = 1,000 × kVA ÷ (√3 × V)
- Apparent power is the product of rms voltage and rms current, and is measured in volt-amperes; real power is apparent power times the power factor. Source: IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities.
- A three-phase load of 900 VA on a 230 V phase supply draws 1.304 A per line (Fiore, Example 9.2). Source: AC Electrical Circuit Analysis, §9.4 Power Factor Correction.
Full-load current of common kVA sizes
Current per line at full rating. Sizes are common transformer and generator ratings.
| kVA | 240 V single | 208 V three | 400 V three | 480 V three |
|---|---|---|---|---|
| 5 kVA | 20.8 A | 13.9 A | 7.22 A | 6.01 A |
| 10 kVA | 41.7 A | 27.8 A | 14.4 A | 12 A |
| 15 kVA | 62.5 A | 41.6 A | 21.7 A | 18 A |
| 25 kVA | 104 A | 69.4 A | 36.1 A | 30.1 A |
| 30 kVA | 125 A | 83.3 A | 43.3 A | 36.1 A |
| 45 kVA | 188 A | 125 A | 65 A | 54.1 A |
| 50 kVA | 208 A | 139 A | 72.2 A | 60.1 A |
| 75 kVA | 313 A | 208 A | 108 A | 90.2 A |
| 100 kVA | 417 A | 278 A | 144 A | 120 A |
| 112.5 kVA | 469 A | 312 A | 162 A | 135 A |
Show all 14 rowsShow fewer
| 150 kVA | 625 A | 416 A | 217 A | 180 A |
| 225 kVA | 938 A | 625 A | 325 A | 271 A |
| 300 kVA | 1,250 A | 833 A | 433 A | 361 A |
| 500 kVA | 2,080 A | 1,390 A | 722 A | 601 A |
Common questions
How many amps is a 100 kVA generator?
At 480 V three phase, 120 A per line; at 400 V, 144 A; at 208 V, 278 A. A 100 kVA set rated at a power factor of 0.8 supplies at most 80 kW of real power.
Is kVA the same as kW?
Only when the power factor is 1. kVA is volts times amps; kW is the real power, kVA times the power factor. A 50 kVA supply feeding motors at a power factor of 0.85 delivers 42.5 kW.
Why does a transformer use kVA and not kW?
Its losses and heating come from the current through its windings, whatever the power factor of the load. Rating it in kVA describes what it can carry without knowing what will be connected.