kVA to Amps Calculator

The full-load current of a transformer or generator from its kVA rating and voltage.

The full-load current of a transformer or generator from its kVA rating and voltage. kVA counts all the current, whatever the power factor.

V
Common
More optionsVoltage measured line to line; switch to line to neutral

ExampleCurrent per line

208.2A

A 75 kVA rating on a 208 V three-phase supply means up to 208.2 A in each line at full load.

Enter your own values to see your result.

L1L2L3208 VN120.1 V to neutral208.2 A each75 kVA

Each line carries the same current, a third of a cycle apart.

Real power at PF 0.8
60 kW
Line to neutral
120.1 V
At 400 V
108.3 A

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms

How this works: 8 sources,

How this works

Method

A kVA rating is the current a transformer or generator can deliver times its voltage, so the full-load current is the kVA divided by the voltage. For a 25 kVA single-phase transformer on 240 V that is 25,000 ÷ 240 = 104 A. No power factor comes into it: kVA already counts all the current, the part doing work and the part that isn’t. Full method

How it’s tested

2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.

Every change on What’s new

How we make toolsReport a mistake

How to work out amps from kVA

A kVA rating is the current a transformer or generator can deliver times its voltage, so the full-load current is the kVA divided by the voltage. For a 25 kVA single-phase transformer on 240 V that is 25,000 ÷ 240 = 104 A. No power factor comes into it: kVA already counts all the current, the part doing work and the part that isn’t.

For three phase, divide by √3 times the voltage between lines. A 75 kVA transformer at 208 V gives 75,000 ÷ (1.732 × 208) = 208 A per line; the same 75 kVA at 480 V is 90 A. That is why a building’s 480 V side has much smaller conductors than its 208 V side for the same kVA.

The real power a kVA rating can supply depends on the load. At a power factor of 0.8, which is the rating point for many generators, 75 kVA delivers 60 kW. That is why generator sets often show both: 100 kVA / 80 kW.

Single phase: I = 1,000 × kVA ÷ V · three phase: I = 1,000 × kVA ÷ (√3 × V)

Full-load current of common kVA sizes

Current per line at full rating. Sizes are common transformer and generator ratings.

Current per line at full rating. Sizes are common transformer and generator ratings.
kVA240 V single208 V three400 V three480 V three
5 kVA20.8 A13.9 A7.22 A6.01 A
10 kVA41.7 A27.8 A14.4 A12 A
15 kVA62.5 A41.6 A21.7 A18 A
25 kVA104 A69.4 A36.1 A30.1 A
30 kVA125 A83.3 A43.3 A36.1 A
45 kVA188 A125 A65 A54.1 A
50 kVA208 A139 A72.2 A60.1 A
75 kVA313 A208 A108 A90.2 A
100 kVA417 A278 A144 A120 A
112.5 kVA469 A312 A162 A135 A
Show all 14 rows
150 kVA625 A416 A217 A180 A
225 kVA938 A625 A325 A271 A
300 kVA1,250 A833 A433 A361 A
500 kVA2,080 A1,390 A722 A601 A

Common questions

How many amps is a 100 kVA generator?

At 480 V three phase, 120 A per line; at 400 V, 144 A; at 208 V, 278 A. A 100 kVA set rated at a power factor of 0.8 supplies at most 80 kW of real power.

Is kVA the same as kW?

Only when the power factor is 1. kVA is volts times amps; kW is the real power, kVA times the power factor. A 50 kVA supply feeding motors at a power factor of 0.85 delivers 42.5 kW.

Why does a transformer use kVA and not kW?

Its losses and heating come from the current through its windings, whatever the power factor of the load. Rating it in kVA describes what it can carry without knowing what will be connected.