Three-Phase Power Calculator
Real and apparent power in a three-phase circuit from the line current…
Real and apparent power in a three-phase circuit from the line current, the voltage between lines and the power factor, with the √3 explained.
The current in each line, for a balanced load.
1 for heaters, kettles and lamps; often 0.7 to 0.9 for motors.
More optionsVoltage measured line to line; switch to line to neutral
ExampleReal power
37.41kW
50 A in each line from a 480 V three-phase supply at a power factor of 0.9 delivers 37.41 kW.
Enter your own values to see your result.
Each line carries the same current, a third of a cycle apart.
- Apparent power
- 41.57 kVA
- Line to neutral
- 277.1 V
- Reactive power
- 18.12 kvar
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms
How this works: 9 sources,
How this works
Method
A three-phase supply has three lines whose voltages peak a third of a cycle apart. In a balanced load each line carries the same current, and the total power is √3 × V × I × PF, where V is the voltage between two lines. For 50 A at 480 V and a power factor of 0.9, that is 1.732 × 480 × 50 × 0.9 = 37.4 kW, from 41.6 kVA of apparent power. Full method
Sources
- AC Electrical Circuit Analysis, §9.4 Power Factor Correction (James M. Fiore, LibreTexts)
- AC Electrical Circuit Analysis, §9.3 Three-Phase Connections (James M. Fiore, LibreTexts)
- IEC 60038:2009+AMD1:2021, IEC standard voltages (IEC, 2009)
- Mains electricity by country (Wikipedia)
- University Physics Volume 2, §9.4 Ohm’s Law (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §9.5 Electrical Energy and Power (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §15.4 Power in an AC Circuit (OpenStax (Ling, Sanny and Moebs), 2016)
- The International System of Units (SI Brochure), 9th edition (BIPM, 2019)
- IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities (IEEE, 2010)
How it’s tested
2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.
How three-phase power is calculated
A three-phase supply has three lines whose voltages peak a third of a cycle apart. In a balanced load each line carries the same current, and the total power is √3 × V × I × PF, where V is the voltage between two lines. For 50 A at 480 V and a power factor of 0.9, that is 1.732 × 480 × 50 × 0.9 = 37.4 kW, from 41.6 kVA of apparent power.
The √3 comes from the geometry of the three phases. Each line-to-neutral voltage is 1/√3 of the line-to-line voltage (277 V on a 480 V system), and three phases each carry V_LN × I × PF, so the total is 3 × 277 × 50 × 0.9, the same 37.4 kW. Use whichever voltage you know; the calculator lets you choose.
The formula assumes a balanced load, the same current in each line. Real buildings rarely balance exactly; for an unbalanced load, add up the power of each phase from its own current and line-to-neutral voltage.
P = √3 × V_LL × I × PF = 3 × V_LN × I × PF · S = √3 × V_LL × I · Q = √(S² − P²)
- In Fiore’s Example 9.1, a balanced load at 207.8 V between lines and a power factor of 0.9357 takes 1,134 W of real power and 1,212 VA of apparent power. Source: AC Electrical Circuit Analysis, §9.4 Power Factor Correction.
- The line voltage of a balanced three-phase system is √3 times the phase voltage, with the line voltages 120° apart. Source: AC Electrical Circuit Analysis, §9.3 Three-Phase Connections.
- IEC 60038 lists 230/400 V and 400/690 V as standard three-phase low voltages. Source: IEC 60038:2009+AMD1:2021, IEC standard voltages.
- North America distributes 208Y/120 V and 480Y/277 V three phase to buildings, while most of the world uses 230/400 V. Source: Mains electricity by country.
Common three-phase systems
Line-to-line and line-to-neutral voltages, and the real power 100 A per line carries at a power factor of 1.
| System | Line to line | Line to neutral | kW at 100 A | Where |
|---|---|---|---|---|
| 208Y/120 V | 208 V | 120 V | 36 kW | North America, buildings |
| 480Y/277 V | 480 V | 277 V | 83.1 kW | North America, commercial |
| 600Y/347 V | 600 V | 346 V | 104 kW | Canada, industrial |
| 230/400 V | 400 V | 231 V | 69.3 kW | IEC standard, Europe and much of the world |
| 240/415 V | 415 V | 240 V | 71.9 kW | Older UK and Australian systems |
| 220/380 V | 380 V | 219 V | 65.8 kW | China and others |
| 127/220 V | 220 V | 127 V | 38.1 kW | Parts of Latin America |
| 400/690 V | 690 V | 398 V | 120 kW | IEC standard, industrial |
Common questions
Why multiply by √3 and not 3?
Because the voltage you usually know is the one between two lines, which is √3 times each phase’s voltage to neutral. Three phases × the phase voltage = 3 × V_LL ÷ √3 = √3 × V_LL. With the line-to-neutral voltage, multiply by 3.
Is the current the same in each line?
In a balanced load, yes, and that is what this calculator assumes: the current you enter flows in each of the three lines. It is not the total of the three.
What is the difference between kW and kVA here?
kVA is √3 × V × I, all the current the lines carry. kW is the part that does work, kVA × power factor. The difference is reactive power (kvar), which motors need for their magnetic fields; the power factor page shows how capacitors supply it locally.
Is 400 V the same as 415 V or 380 V?
They are the same kind of system at different nominal voltages. Europe and the IEC standard moved to 230/400 V, replacing 240/415 V and 220/380 V; supplies vary within a tolerance band around the nominal value either way.