Three-Phase Power Calculator

Real and apparent power in a three-phase circuit from the line current…

Real and apparent power in a three-phase circuit from the line current, the voltage between lines and the power factor, with the √3 explained.

A

The current in each line, for a balanced load.

V
Common
Common

1 for heaters, kettles and lamps; often 0.7 to 0.9 for motors.

More optionsVoltage measured line to line; switch to line to neutral

ExampleReal power

37.41kW

50 A in each line from a 480 V three-phase supply at a power factor of 0.9 delivers 37.41 kW.

Enter your own values to see your result.

L1L2L3480 VN277.1 V to neutral50 A each37.41 kW

Each line carries the same current, a third of a cycle apart.

Apparent power
41.57 kVA
Line to neutral
277.1 V
Reactive power
18.12 kvar

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms

How this works: 9 sources,

How this works

Method

A three-phase supply has three lines whose voltages peak a third of a cycle apart. In a balanced load each line carries the same current, and the total power is √3 × V × I × PF, where V is the voltage between two lines. For 50 A at 480 V and a power factor of 0.9, that is 1.732 × 480 × 50 × 0.9 = 37.4 kW, from 41.6 kVA of apparent power. Full method

How it’s tested

2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.

Every change on What’s new

How we make toolsReport a mistake

How three-phase power is calculated

A three-phase supply has three lines whose voltages peak a third of a cycle apart. In a balanced load each line carries the same current, and the total power is √3 × V × I × PF, where V is the voltage between two lines. For 50 A at 480 V and a power factor of 0.9, that is 1.732 × 480 × 50 × 0.9 = 37.4 kW, from 41.6 kVA of apparent power.

The √3 comes from the geometry of the three phases. Each line-to-neutral voltage is 1/√3 of the line-to-line voltage (277 V on a 480 V system), and three phases each carry V_LN × I × PF, so the total is 3 × 277 × 50 × 0.9, the same 37.4 kW. Use whichever voltage you know; the calculator lets you choose.

The formula assumes a balanced load, the same current in each line. Real buildings rarely balance exactly; for an unbalanced load, add up the power of each phase from its own current and line-to-neutral voltage.

P = √3 × V_LL × I × PF = 3 × V_LN × I × PF · S = √3 × V_LL × I · Q = √(S² − P²)

Common three-phase systems

Line-to-line and line-to-neutral voltages, and the real power 100 A per line carries at a power factor of 1.

Line-to-line and line-to-neutral voltages, and the real power 100 A per line carries at a power factor of 1.
SystemLine to lineLine to neutralkW at 100 AWhere
208Y/120 V208 V120 V36 kWNorth America, buildings
480Y/277 V480 V277 V83.1 kWNorth America, commercial
600Y/347 V600 V346 V104 kWCanada, industrial
230/400 V400 V231 V69.3 kWIEC standard, Europe and much of the world
240/415 V415 V240 V71.9 kWOlder UK and Australian systems
220/380 V380 V219 V65.8 kWChina and others
127/220 V220 V127 V38.1 kWParts of Latin America
400/690 V690 V398 V120 kWIEC standard, industrial

Common questions

Why multiply by √3 and not 3?

Because the voltage you usually know is the one between two lines, which is √3 times each phase’s voltage to neutral. Three phases × the phase voltage = 3 × V_LL ÷ √3 = √3 × V_LL. With the line-to-neutral voltage, multiply by 3.

Is the current the same in each line?

In a balanced load, yes, and that is what this calculator assumes: the current you enter flows in each of the three lines. It is not the total of the three.

What is the difference between kW and kVA here?

kVA is √3 × V × I, all the current the lines carry. kW is the part that does work, kVA × power factor. The difference is reactive power (kvar), which motors need for their magnetic fields; the power factor page shows how capacitors supply it locally.

Is 400 V the same as 415 V or 380 V?

They are the same kind of system at different nominal voltages. Europe and the IEC standard moved to 230/400 V, replacing 240/415 V and 220/380 V; supplies vary within a tolerance band around the nominal value either way.