kW to Amps Calculator

The current a load in kilowatts draws on a single-phase or three-phase supply.

The current a load in kilowatts draws on a single-phase or three-phase supply. Three phase shares the power between three lines, so each carries less.

V
Common
Common

1 for heaters, kettles and lamps; often 0.7 to 0.9 for motors.

More optionsVoltage measured line to line; switch to line to neutral

ExampleCurrent per line

15.88A

A 11 kW load on a 400 V three-phase supply draws 15.88 A in each line.

Enter your own values to see your result.

L1L2L3400 VN230.9 V to neutral15.88 A each11 kW

Each line carries the same current, a third of a cycle apart.

Apparent power
11 kVA
Line to neutral
230.9 V
At 480 V
13.23 A

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms

How this works: 8 sources,

How this works

Method

Turn the kilowatts into watts (× 1,000), then divide by the voltage, the power factor and, on three phase, √3. An 11 kW EV charger on a 400 V three-phase supply draws 11,000 ÷ (1.732 × 400 × 1) = 15.9 A in each line, which is why it is sold as a 16 A three-phase unit. The same 11 kW from one 230 V phase would need 47.8 A. Full method

How it’s tested

2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.

Every change on What’s new

How we make toolsReport a mistake

How to convert kW to amps

Turn the kilowatts into watts (× 1,000), then divide by the voltage, the power factor and, on three phase, √3. An 11 kW EV charger on a 400 V three-phase supply draws 11,000 ÷ (1.732 × 400 × 1) = 15.9 A in each line, which is why it is sold as a 16 A three-phase unit. The same 11 kW from one 230 V phase would need 47.8 A.

The power factor matters most for motors. A 22 kW motor is rated by the mechanical power at its shaft, so divide by its efficiency first to get the electrical power it draws, then use its power factor: at 92% efficiency and 0.86, that is 22 ÷ 0.92 = 23.9 kW of input and 23,900 ÷ (1.732 × 400 × 0.86) = 40.1 A.

Use the voltage between lines on a three-phase supply (208 V, 400 V, 480 V), not the line-to-neutral one. If you only know the line-to-neutral voltage, switch the reference under More options: the calculator then divides by 3 times that voltage, which gives the same current.

I = 1,000 × kW ÷ (V × PF) · three phase: I = 1,000 × kW ÷ (√3 × V × PF)

kW to amps, single and three phase

Current per line at a power factor of 1. For motors, use their electrical input power and power factor.

Current per line at a power factor of 1. For motors, use their electrical input power and power factor.
kW230 V single208 V three400 V three480 V three
1 kW4.35 A2.78 A1.44 A1.2 A
2.2 kW9.57 A6.11 A3.18 A2.65 A
3 kW13 A8.33 A4.33 A3.61 A
3.7 kW16.1 A10.3 A5.34 A4.45 A
5.5 kW23.9 A15.3 A7.94 A6.62 A
7.4 kW32.2 A20.5 A10.7 A8.9 A
11 kW47.8 A30.5 A15.9 A13.2 A
15 kW65.2 A41.6 A21.7 A18 A
22 kW95.7 A61.1 A31.8 A26.5 A
30 kW130 A83.3 A43.3 A36.1 A
Show all 13 rows
50 kW217 A139 A72.2 A60.1 A
75 kW326 A208 A108 A90.2 A
100 kW435 A278 A144 A120 A

Common questions

How many amps is 7.4 kW?

32.2 A on a 230 V single-phase supply, the usual home EV charger, and 30.8 A at 240 V. On a 400 V three-phase supply 7.4 kW would be only 10.7 A per line.

Why is three phase less current for the same kW?

Three lines share the load, and the voltage between any two of them is √3 times the voltage to neutral. Per line, the current is the power divided by √3 × V × PF: about a third of what one phase at the line-to-neutral voltage would carry.

Do I use the motor’s kW rating as is?

Motor nameplates give the output at the shaft. The electrical power going in is higher by the motor’s losses, so divide by its efficiency (often 85% to 95%) before converting, and use its power factor at full load; the nameplate current is the best check.