Power Factor Calculator
What a power factor means for current and kVA…
What a power factor means for current and kVA, and how much capacitor power brings it up to a target such as 0.95. The triangle redraws as you type.
Supply (for amps and µF)Three phase, capacitors in delta, 400 V, 50 Hz
ExampleCapacitor needed
27.7kvar
To raise 50 kW from 0.75 to 0.95, add 27.7 kvar of capacitors. The supply then carries 52.6 kVA instead of 66.7 kVA, and the heat lost in the cables feeding it falls by 38%.
Enter your own load to see your result.
Dashed: before. Filled: after the capacitors supply part of the reactive power.
- Power factor now
- 0.75 (66.7 kVA, 44.1 kvar)
- Current per line at 400 V
- 96.23 A → 75.97 A
- Capacitance, each of 3 in delta
- 183.4 µF
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms
How this works: 8 sources,
How this works
Method
Power factor is real power divided by apparent power: kW ÷ kVA, or the cosine of the angle φ between voltage and current. A motor taking 50 kW at a power factor of 0.75 makes the supply carry 50 ÷ 0.75 = 66.7 kVA. The difference is reactive power, √(66.7² − 50²) = 44.1 kvar, which flows back and forth to build the motor’s magnetic field and does no work, but still heats cables and transformers. Full method
Sources
- AC Electrical Circuit Analysis, §9.4 Power Factor Correction (James M. Fiore, LibreTexts)
- IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities (IEEE, 2010)
- University Physics Volume 2, §9.4 Ohm’s Law (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §9.5 Electrical Energy and Power (OpenStax (Ling, Sanny and Moebs), 2016)
- University Physics Volume 2, §15.4 Power in an AC Circuit (OpenStax (Ling, Sanny and Moebs), 2016)
- The International System of Units (SI Brochure), 9th edition (BIPM, 2019)
- AC Electrical Circuit Analysis, §9.3 Three-Phase Connections (James M. Fiore, LibreTexts)
- IEC 60038:2009+AMD1:2021, IEC standard voltages (IEC, 2009)
How it’s tested
4 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: Ohm’s law from any two values with a live circuit and the formula wheel, plus watts to amps, amps to watts, kW and kVA to amps, three-phase power and power factor pages.
Power factor and how to correct it
Power factor is real power divided by apparent power: kW ÷ kVA, or the cosine of the angle φ between voltage and current. A motor taking 50 kW at a power factor of 0.75 makes the supply carry 50 ÷ 0.75 = 66.7 kVA. The difference is reactive power, √(66.7² − 50²) = 44.1 kvar, which flows back and forth to build the motor’s magnetic field and does no work, but still heats cables and transformers.
Capacitors supply that reactive power locally, so less of it travels from the supply. To reach a target power factor, the capacitor must supply Qc = P × (tan φ1 − tan φ2): for 50 kW from 0.75 to 0.95, 50 × (0.882 − 0.329) = 27.7 kvar. The kVA falls to 52.6 and the current falls by about a fifth, while the real power stays the same.
The capacitance follows from Qc = 2π f C V². For three phase with three capacitors in delta, each carries a third of Qc at the line voltage. Industrial correction is usually bought by kvar at the supply voltage, and harmonics, resonance and over-correction need a proper study; the numbers here are the starting point.
PF = P ÷ S = cos φ · Q = √(S² − P²) · Qc = P × (tan φ1 − tan φ2) · C = Qc ÷ (2π f V²)
- A three-phase load of 900 VA at 0.85 lagging on 230 V phases is corrected to 1 with three 3.17 µF capacitors in delta, cutting the line current from 1.304 A to 1.109 A (Fiore, Example 9.2). Source: AC Electrical Circuit Analysis, §9.4 Power Factor Correction.
- IEEE 1459 defines the power factor as the ratio of active power P to apparent power S. Source: IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities.
What each power factor costs, per kW
For every kW of real power: the kVA and kvar the supply carries, how much more current than at a power factor of 1, and the capacitor kvar to reach 0.95.
| Power factor | kVA per kW | kvar per kW | Extra current | kvar to 0.95 |
|---|---|---|---|---|
| 1 | 1 | 0 | 0% | none |
| 0.95 | 1.05 | 0.329 | 5.26% | none |
| 0.9 | 1.11 | 0.484 | 11.1% | 0.156 |
| 0.85 | 1.18 | 0.62 | 17.6% | 0.291 |
| 0.8 | 1.25 | 0.75 | 25% | 0.421 |
| 0.75 | 1.33 | 0.882 | 33.3% | 0.553 |
| 0.7 | 1.43 | 1.02 | 42.9% | 0.692 |
| 0.65 | 1.54 | 1.17 | 53.8% | 0.84 |
| 0.6 | 1.67 | 1.33 | 66.7% | 1 |
| 0.5 | 2 | 1.73 | 100% | 1.4 |
Common questions
What is a good power factor?
Close to 1. Many utilities bill commercial customers extra below about 0.9 or 0.95, and those are common targets for correction. Heaters and lamps are near 1; lightly loaded motors can be 0.5 or lower.
Does correcting power factor save energy?
It reduces the current, so it cuts the heating losses in cables and transformers between the capacitor and the supply, and it can remove a utility’s reactive power charges. The load itself uses the same real power as before.
Can the power factor be too high?
Going past 1 with too much capacitance makes the load leading, which also raises the current and can push voltages up when the load is light. Correction is usually sized to around 0.95, often in steps that switch with the load.
Lagging or leading: which is this?
This calculator assumes a lagging power factor, the usual case for motors, transformers and fluorescent ballasts, where current trails voltage and capacitors correct it.