AWG to mm² Converter and Wire Gauge Chart

The cross-section, diameter and resistance of any AWG size, the nearest metric size…

The cross-section, diameter and resistance of any AWG size, the nearest metric size, and the full gauge chart from 4/0 down to 40.

Wire size

Switch AWG and mm² above the list to convert the other way.

12 AWG in mm²

3.31mm²

12 AWG is 2.05 mm (0.0808 in) across and 3.31 mm² in area (6,530 circular mils). The nearest metric size is 4 mm².

2.5 mm²12 AWG4 mm²Drawn to scale, as solid round copper
Diameter
2.05 mm · 0.0808 in
Copper at 20 °C
5.21 Ω/km · 1.59 Ω/1,000 ft
Aluminium at 20 °C
8.54 Ω/km · 2.6 Ω/1,000 ft
How this works: 6 sources,

How this works

Method

AWG numbers count drawing steps, so a bigger number is a thinner wire. ASTM B258 fixes the sizes with one rule: 36 AWG is 0.005 inch across, 0000 (4/0) is 0.46 inch, and there are 39 equal steps for every factor of 92 in diameter. Every 6 gauges the diameter halves; every 3 gauges the area halves. So 12 AWG is 0.0808 in (2.05 mm) across and 3.31 mm² in area. Full method

How it’s tested

3 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.

Every change on What’s new

How we make toolsReport a mistake

How AWG sizes convert to mm²

AWG numbers count drawing steps, so a bigger number is a thinner wire. ASTM B258 fixes the sizes with one rule: 36 AWG is 0.005 inch across, 0000 (4/0) is 0.46 inch, and there are 39 equal steps for every factor of 92 in diameter. Every 6 gauges the diameter halves; every 3 gauges the area halves. So 12 AWG is 0.0808 in (2.05 mm) across and 3.31 mm² in area.

Metric cables are named by their area in mm² (IEC 60228), so converting is a matter of areas: 12 AWG (3.31 mm²) falls between 2.5 and 4 mm², 10 AWG (5.26 mm²) between 4 and 6. AWG and metric sizes never line up exactly, which matters when swapping one for the other.

Above 4/0, North America names sizes by area in thousands of circular mils (kcmil). A circular mil is the area of a circle 1 mil (0.001 in) across, so a solid wire’s area in circular mils is just its diameter in mils squared: 10 AWG is 101.9², about 10,380 cmil.

d = 0.005 in × 92^((36 − n) ÷ 39) · A = π ÷ 4 × d² · 1 cmil = 0.000507 mm²

AWG wire gauge chart

Diameter and area of solid wire, and copper’s resistance at 20 °C, from the ASTM B258 rule and the annealed copper standard. Stranded wire of the same gauge has about the same area and a larger diameter.

Diameter and area of solid wire, and copper’s resistance at 20 °C, from the ASTM B258 rule and the annealed copper standard. Stranded wire of the same gauge has about the same area and a larger diameter.
AWGDiameter (mm)Diameter (in)Area (mm²)Copper Ω/kmCopper Ω/1,000 ft
4/011.70.461070.1610.049
3/010.40.41850.2030.0618
2/09.270.36567.40.2560.0779
1/08.250.32553.50.3220.0983
17.350.28942.40.4070.124
26.540.25833.60.5130.156
35.830.22926.70.6460.197
45.190.20421.20.8150.248
54.620.18216.81.030.313
64.120.16213.31.30.395
73.660.14410.51.630.498
83.260.1288.372.060.628
92.910.1146.632.60.792
102.590.1025.263.280.999
Show all 44 rows
112.30.09074.174.131.26
122.050.08083.315.211.59
131.830.0722.626.572
141.630.06412.088.292.53
151.450.05711.6510.43.18
161.290.05081.3113.24.02
171.150.04531.0416.65.06
181.020.04030.82320.96.39
190.9120.03590.65326.48.05
200.8120.0320.51833.310.2
210.7230.02850.414212.8
220.6440.02530.3265316.1
230.5730.02260.25866.820.4
240.5110.02010.20584.225.7
250.4550.01790.16210632.4
260.4050.01590.12913440.8
270.3610.01420.10216951.5
280.3210.01260.08121364.9
290.2860.01130.064226881.8
300.2550.010.0509339103
310.2270.008930.0404427130
320.2020.007950.032538164
330.180.007080.0254679207
340.160.00630.0201856261
350.1430.005610.0161,080329
360.1270.0050.01271,360415
370.1130.004450.011,720523
380.1010.003970.007972,160660
390.08970.003530.006322,730832
400.07990.003140.005013,4401,050

Common questions

Is 12 AWG the same as 2.5 mm² or 4 mm²?

Neither: 12 AWG is 3.31 mm², between the two. 2.5 mm² is closest to 13 AWG and 4 mm² to 11 AWG. Use the actual areas when comparing resistance or voltage drop.

Why do smaller AWG numbers mean thicker wire?

The numbers come from how many times the wire was drawn through a die: each pass made it thinner. 4/0 (0000) is the thickest gauge size, then kcmil sizes take over.

Does stranded wire have the same mm²?

About the same conducting area for the same gauge, but a larger overall diameter because of the gaps between strands, and slightly higher resistance. Flexible cords use more, finer strands.

Can I use this chart to choose a wire for a circuit?

No. This chart gives sizes and resistance. How much current a wire may carry depends on its insulation rating, installation and the rules where you are; those tables are not here on purpose.