AWG to mm² Converter and Wire Gauge Chart
The cross-section, diameter and resistance of any AWG size, the nearest metric size…
The cross-section, diameter and resistance of any AWG size, the nearest metric size, and the full gauge chart from 4/0 down to 40.
Switch AWG and mm² above the list to convert the other way.
12 AWG in mm²
3.31mm²
12 AWG is 2.05 mm (0.0808 in) across and 3.31 mm² in area (6,530 circular mils). The nearest metric size is 4 mm².
- Diameter
- 2.05 mm · 0.0808 in
- Copper at 20 °C
- 5.21 Ω/km · 1.59 Ω/1,000 ft
- Aluminium at 20 °C
- 8.54 Ω/km · 2.6 Ω/1,000 ft
How this works: 6 sources,
How this works
Method
AWG numbers count drawing steps, so a bigger number is a thinner wire. ASTM B258 fixes the sizes with one rule: 36 AWG is 0.005 inch across, 0000 (4/0) is 0.46 inch, and there are 39 equal steps for every factor of 92 in diameter. Every 6 gauges the diameter halves; every 3 gauges the area halves. So 12 AWG is 0.0808 in (2.05 mm) across and 3.31 mm² in area. Full method
Sources
- Copper Wire Tables, Handbook 100 (resistivity 0.017241 Ω·mm²/m and α 0.00393 at 20 °C; AWG tables) (National Bureau of Standards (NIST), 1966)
- ASTM B258, Standard nominal diameters and cross-sectional areas of AWG sizes of solid round wires (ASTM International)
- IEC 60228:2023, Conductors of insulated cables (nominal sizes 0.5 to 3,500 mm²) (IEC, 2023)
- Aluminum Wire Tables, Handbook 109 (EC-H19 at 61% IACS: 0.028264 Ω·mm²/m, α 0.00403) (National Bureau of Standards (NIST), 1972)
- IEC 60364-5-52:2009+AMD1:2024, Annex G (informative): voltage drop in consumers’ installations (IEC)
- Electrical Installation Guide: maximum voltage drop limit (Schneider Electric)
How it’s tested
3 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.
How AWG sizes convert to mm²
AWG numbers count drawing steps, so a bigger number is a thinner wire. ASTM B258 fixes the sizes with one rule: 36 AWG is 0.005 inch across, 0000 (4/0) is 0.46 inch, and there are 39 equal steps for every factor of 92 in diameter. Every 6 gauges the diameter halves; every 3 gauges the area halves. So 12 AWG is 0.0808 in (2.05 mm) across and 3.31 mm² in area.
Metric cables are named by their area in mm² (IEC 60228), so converting is a matter of areas: 12 AWG (3.31 mm²) falls between 2.5 and 4 mm², 10 AWG (5.26 mm²) between 4 and 6. AWG and metric sizes never line up exactly, which matters when swapping one for the other.
Above 4/0, North America names sizes by area in thousands of circular mils (kcmil). A circular mil is the area of a circle 1 mil (0.001 in) across, so a solid wire’s area in circular mils is just its diameter in mils squared: 10 AWG is 101.9², about 10,380 cmil.
d = 0.005 in × 92^((36 − n) ÷ 39) · A = π ÷ 4 × d² · 1 cmil = 0.000507 mm²
- NBS Handbook 100 lists 10 AWG at 101.9 mils and 10,380 circular mils, with 0.9988 Ω per 1,000 ft in annealed copper at 20 °C; this page’s formula gives the same to four figures. Source: Copper Wire Tables, Handbook 100 (resistivity 0.017241 Ω·mm²/m and α 0.00393 at 20 °C; AWG tables).
- ASTM B258 sets the nominal diameters and areas of AWG sizes from the gauge’s geometric rule. Source: ASTM B258, Standard nominal diameters and cross-sectional areas of AWG sizes of solid round wires.
- IEC 60228 sets the nominal cross-sections of cable conductors from 0.5 to 3,500 mm². Source: IEC 60228:2023, Conductors of insulated cables (nominal sizes 0.5 to 3,500 mm²).
AWG wire gauge chart
Diameter and area of solid wire, and copper’s resistance at 20 °C, from the ASTM B258 rule and the annealed copper standard. Stranded wire of the same gauge has about the same area and a larger diameter.
| AWG | Diameter (mm) | Diameter (in) | Area (mm²) | Copper Ω/km | Copper Ω/1,000 ft |
|---|---|---|---|---|---|
| 4/0 | 11.7 | 0.46 | 107 | 0.161 | 0.049 |
| 3/0 | 10.4 | 0.41 | 85 | 0.203 | 0.0618 |
| 2/0 | 9.27 | 0.365 | 67.4 | 0.256 | 0.0779 |
| 1/0 | 8.25 | 0.325 | 53.5 | 0.322 | 0.0983 |
| 1 | 7.35 | 0.289 | 42.4 | 0.407 | 0.124 |
| 2 | 6.54 | 0.258 | 33.6 | 0.513 | 0.156 |
| 3 | 5.83 | 0.229 | 26.7 | 0.646 | 0.197 |
| 4 | 5.19 | 0.204 | 21.2 | 0.815 | 0.248 |
| 5 | 4.62 | 0.182 | 16.8 | 1.03 | 0.313 |
| 6 | 4.12 | 0.162 | 13.3 | 1.3 | 0.395 |
| 7 | 3.66 | 0.144 | 10.5 | 1.63 | 0.498 |
| 8 | 3.26 | 0.128 | 8.37 | 2.06 | 0.628 |
| 9 | 2.91 | 0.114 | 6.63 | 2.6 | 0.792 |
| 10 | 2.59 | 0.102 | 5.26 | 3.28 | 0.999 |
Show all 44 rowsShow fewer
| 11 | 2.3 | 0.0907 | 4.17 | 4.13 | 1.26 |
| 12 | 2.05 | 0.0808 | 3.31 | 5.21 | 1.59 |
| 13 | 1.83 | 0.072 | 2.62 | 6.57 | 2 |
| 14 | 1.63 | 0.0641 | 2.08 | 8.29 | 2.53 |
| 15 | 1.45 | 0.0571 | 1.65 | 10.4 | 3.18 |
| 16 | 1.29 | 0.0508 | 1.31 | 13.2 | 4.02 |
| 17 | 1.15 | 0.0453 | 1.04 | 16.6 | 5.06 |
| 18 | 1.02 | 0.0403 | 0.823 | 20.9 | 6.39 |
| 19 | 0.912 | 0.0359 | 0.653 | 26.4 | 8.05 |
| 20 | 0.812 | 0.032 | 0.518 | 33.3 | 10.2 |
| 21 | 0.723 | 0.0285 | 0.41 | 42 | 12.8 |
| 22 | 0.644 | 0.0253 | 0.326 | 53 | 16.1 |
| 23 | 0.573 | 0.0226 | 0.258 | 66.8 | 20.4 |
| 24 | 0.511 | 0.0201 | 0.205 | 84.2 | 25.7 |
| 25 | 0.455 | 0.0179 | 0.162 | 106 | 32.4 |
| 26 | 0.405 | 0.0159 | 0.129 | 134 | 40.8 |
| 27 | 0.361 | 0.0142 | 0.102 | 169 | 51.5 |
| 28 | 0.321 | 0.0126 | 0.081 | 213 | 64.9 |
| 29 | 0.286 | 0.0113 | 0.0642 | 268 | 81.8 |
| 30 | 0.255 | 0.01 | 0.0509 | 339 | 103 |
| 31 | 0.227 | 0.00893 | 0.0404 | 427 | 130 |
| 32 | 0.202 | 0.00795 | 0.032 | 538 | 164 |
| 33 | 0.18 | 0.00708 | 0.0254 | 679 | 207 |
| 34 | 0.16 | 0.0063 | 0.0201 | 856 | 261 |
| 35 | 0.143 | 0.00561 | 0.016 | 1,080 | 329 |
| 36 | 0.127 | 0.005 | 0.0127 | 1,360 | 415 |
| 37 | 0.113 | 0.00445 | 0.01 | 1,720 | 523 |
| 38 | 0.101 | 0.00397 | 0.00797 | 2,160 | 660 |
| 39 | 0.0897 | 0.00353 | 0.00632 | 2,730 | 832 |
| 40 | 0.0799 | 0.00314 | 0.00501 | 3,440 | 1,050 |
Common questions
Is 12 AWG the same as 2.5 mm² or 4 mm²?
Neither: 12 AWG is 3.31 mm², between the two. 2.5 mm² is closest to 13 AWG and 4 mm² to 11 AWG. Use the actual areas when comparing resistance or voltage drop.
Why do smaller AWG numbers mean thicker wire?
The numbers come from how many times the wire was drawn through a die: each pass made it thinner. 4/0 (0000) is the thickest gauge size, then kcmil sizes take over.
Does stranded wire have the same mm²?
About the same conducting area for the same gauge, but a larger overall diameter because of the gaps between strands, and slightly higher resistance. Flexible cords use more, finer strands.
Can I use this chart to choose a wire for a circuit?
No. This chart gives sizes and resistance. How much current a wire may carry depends on its insulation rating, installation and the rules where you are; those tables are not here on purpose.