Wire Resistance Calculator

How many ohms a length of copper or aluminium wire has…

How many ohms a length of copper or aluminium wire has, at the temperature it runs at. Resistance grows with length and heat and shrinks with size.

Of one conductor; the card also gives out and back.

Wire size
°C
Common

Wire warms up under load: 20 °C cool and lightly loaded; 75 °C to 90 °C near full load.

ExampleResistance, one conductor

206.9mΩ

30 m of 2.5 mm² copper at 20 °C has 206.9 mΩ of resistance; out and back (two conductors) it is 413.8 mΩ.

Enter your own wire to see its resistance.

Out and back
413.8 mΩ
Per metre · per foot
6.897 mΩ · 2.102 mΩ
Same size in aluminium
339.2 mΩ

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms

How this works: 6 sources,

How this works

Method

A wire’s resistance is its material’s resistivity times its length, divided by its cross-section: R = ρ × L ÷ A. Copper at 20 °C has ρ = 1/58 Ω·mm²/m, so 30 m of 2.5 mm² copper is 30 ÷ 58 ÷ 2.5 = 0.207 Ω. Twice the length doubles it; twice the area halves it. Full method

How it’s tested

2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.

Every change on What’s new

How we make toolsReport a mistake

How to calculate wire resistance

A wire’s resistance is its material’s resistivity times its length, divided by its cross-section: R = ρ × L ÷ A. Copper at 20 °C has ρ = 1/58 Ω·mm²/m, so 30 m of 2.5 mm² copper is 30 ÷ 58 ÷ 2.5 = 0.207 Ω. Twice the length doubles it; twice the area halves it.

Metals resist more when warm. Copper’s resistance rises 0.393% for each °C above 20 °C and aluminium’s 0.403%, so the same 30 m at 75 °C is 0.207 × 1.216 = 0.252 Ω. That is why voltage drop is worse on a hot, fully loaded cable than a measurement on a cold one suggests.

Aluminium conducts 61% as well as copper, so for the same resistance it needs about 1.64 times the area; it is still lighter and cheaper, which is why it is used for large feeders and overhead lines. Joints in aluminium need connectors rated for it.

R = ρ(T) × L ÷ A · ρ(T) = ρ₂₀ × (1 + α × (T − 20))

Resistance of metric conductors per km at 20 °C

Solid conductor of the nominal area; stranded cables of the same size are within a few percent.

Solid conductor of the nominal area; stranded cables of the same size are within a few percent.
SizeCopper Ω/kmAluminium Ω/kmNearest AWG
0.5 mm²34.556.520 AWG
0.75 mm²2337.718 AWG
1 mm²17.228.317 AWG
1.5 mm²11.518.815 AWG
2.5 mm²6.911.313 AWG
4 mm²4.317.0711 AWG
6 mm²2.874.719 AWG
10 mm²1.722.837 AWG
16 mm²1.081.775 AWG
25 mm²0.691.133 AWG
Show all 19 rows
35 mm²0.4930.8082 AWG
50 mm²0.3450.5651/0 AWG
70 mm²0.2460.4042/0 AWG
95 mm²0.1810.2983/0 AWG
120 mm²0.1440.2364/0 AWG
150 mm²0.1150.1884/0 AWG
185 mm²0.09320.1534/0 AWG
240 mm²0.07180.1184/0 AWG
300 mm²0.05750.09424/0 AWG

Common questions

How do I measure a wire’s resistance?

For short, thick wires the resistance is too small for an ordinary meter (its leads alone are about 0.1 Ω). Use a four-wire (Kelvin) measurement, or pass a known current and measure the voltage across the wire.

Is the resistance of a cable the same as its loop resistance?

No. A circuit has an outgoing and a return conductor, so the loop resistance is twice the single-conductor value for the same size; the card shows both.

How much does temperature matter?

From 20 °C to 90 °C, copper’s resistance rises by about 28%. Use the conductor’s working temperature when the resistance matters, such as for voltage drop or heating.