Wire Resistance Calculator
How many ohms a length of copper or aluminium wire has…
How many ohms a length of copper or aluminium wire has, at the temperature it runs at. Resistance grows with length and heat and shrinks with size.
Of one conductor; the card also gives out and back.
Wire warms up under load: 20 °C cool and lightly loaded; 75 °C to 90 °C near full load.
ExampleResistance, one conductor
206.9mΩ
30 m of 2.5 mm² copper at 20 °C has 206.9 mΩ of resistance; out and back (two conductors) it is 413.8 mΩ.
Enter your own wire to see its resistance.
The same wire as it warms up
- Out and back
- 413.8 mΩ
- Per metre · per foot
- 6.897 mΩ · 2.102 mΩ
- Same size in aluminium
- 339.2 mΩ
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms
How this works: 6 sources,
How this works
Method
A wire’s resistance is its material’s resistivity times its length, divided by its cross-section: R = ρ × L ÷ A. Copper at 20 °C has ρ = 1/58 Ω·mm²/m, so 30 m of 2.5 mm² copper is 30 ÷ 58 ÷ 2.5 = 0.207 Ω. Twice the length doubles it; twice the area halves it. Full method
Sources
- Copper Wire Tables, Handbook 100 (resistivity 0.017241 Ω·mm²/m and α 0.00393 at 20 °C; AWG tables) (National Bureau of Standards (NIST), 1966)
- Aluminum Wire Tables, Handbook 109 (EC-H19 at 61% IACS: 0.028264 Ω·mm²/m, α 0.00403) (National Bureau of Standards (NIST), 1972)
- ASTM B258, Standard nominal diameters and cross-sectional areas of AWG sizes of solid round wires (ASTM International)
- IEC 60228:2023, Conductors of insulated cables (nominal sizes 0.5 to 3,500 mm²) (IEC, 2023)
- IEC 60364-5-52:2009+AMD1:2024, Annex G (informative): voltage drop in consumers’ installations (IEC)
- Electrical Installation Guide: maximum voltage drop limit (Schneider Electric)
How it’s tested
2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.
How to calculate wire resistance
A wire’s resistance is its material’s resistivity times its length, divided by its cross-section: R = ρ × L ÷ A. Copper at 20 °C has ρ = 1/58 Ω·mm²/m, so 30 m of 2.5 mm² copper is 30 ÷ 58 ÷ 2.5 = 0.207 Ω. Twice the length doubles it; twice the area halves it.
Metals resist more when warm. Copper’s resistance rises 0.393% for each °C above 20 °C and aluminium’s 0.403%, so the same 30 m at 75 °C is 0.207 × 1.216 = 0.252 Ω. That is why voltage drop is worse on a hot, fully loaded cable than a measurement on a cold one suggests.
Aluminium conducts 61% as well as copper, so for the same resistance it needs about 1.64 times the area; it is still lighter and cheaper, which is why it is used for large feeders and overhead lines. Joints in aluminium need connectors rated for it.
R = ρ(T) × L ÷ A · ρ(T) = ρ₂₀ × (1 + α × (T − 20))
- The International Annealed Copper Standard resistivity is 0.017241 Ω·mm²/m at 20 °C (1/58), with a temperature coefficient of 0.00393 per °C. Source: Copper Wire Tables, Handbook 100 (resistivity 0.017241 Ω·mm²/m and α 0.00393 at 20 °C; AWG tables).
- Hard-drawn aluminium for conductors (EC-H19, 61% IACS) has a resistivity of 0.028264 Ω·mm²/m at 20 °C and a coefficient of 0.00403 per °C. Source: Aluminum Wire Tables, Handbook 109 (EC-H19 at 61% IACS: 0.028264 Ω·mm²/m, α 0.00403).
Resistance of metric conductors per km at 20 °C
Solid conductor of the nominal area; stranded cables of the same size are within a few percent.
| Size | Copper Ω/km | Aluminium Ω/km | Nearest AWG |
|---|---|---|---|
| 0.5 mm² | 34.5 | 56.5 | 20 AWG |
| 0.75 mm² | 23 | 37.7 | 18 AWG |
| 1 mm² | 17.2 | 28.3 | 17 AWG |
| 1.5 mm² | 11.5 | 18.8 | 15 AWG |
| 2.5 mm² | 6.9 | 11.3 | 13 AWG |
| 4 mm² | 4.31 | 7.07 | 11 AWG |
| 6 mm² | 2.87 | 4.71 | 9 AWG |
| 10 mm² | 1.72 | 2.83 | 7 AWG |
| 16 mm² | 1.08 | 1.77 | 5 AWG |
| 25 mm² | 0.69 | 1.13 | 3 AWG |
Show all 19 rowsShow fewer
| 35 mm² | 0.493 | 0.808 | 2 AWG |
| 50 mm² | 0.345 | 0.565 | 1/0 AWG |
| 70 mm² | 0.246 | 0.404 | 2/0 AWG |
| 95 mm² | 0.181 | 0.298 | 3/0 AWG |
| 120 mm² | 0.144 | 0.236 | 4/0 AWG |
| 150 mm² | 0.115 | 0.188 | 4/0 AWG |
| 185 mm² | 0.0932 | 0.153 | 4/0 AWG |
| 240 mm² | 0.0718 | 0.118 | 4/0 AWG |
| 300 mm² | 0.0575 | 0.0942 | 4/0 AWG |
Common questions
How do I measure a wire’s resistance?
For short, thick wires the resistance is too small for an ordinary meter (its leads alone are about 0.1 Ω). Use a four-wire (Kelvin) measurement, or pass a known current and measure the voltage across the wire.
Is the resistance of a cable the same as its loop resistance?
No. A circuit has an outgoing and a return conductor, so the loop resistance is twice the single-conductor value for the same size; the card shows both.
How much does temperature matter?
From 20 °C to 90 °C, copper’s resistance rises by about 28%. Use the conductor’s working temperature when the resistance matters, such as for voltage drop or heating.