Three-Phase Voltage Drop Calculator

The voltage a balanced three-phase run loses between lines…

The voltage a balanced three-phase run loses between lines, with √3 in place of the 2 of a single-phase circuit, and the heat lost in the three conductors.

V
Common

From the supply to the load, not there and back.

Wire size
Conductor temperature75 °C (a warm conductor near full load)
°C
Common

Wire warms up under load: 20 °C cool and lightly loaded; 75 °C to 90 °C near full load.

ExampleVoltage drop

0.908%

50 m of 16 mm² copper carrying 32 A on 400 V three phase loses 3.632 V, leaving 396.4 V at the load.

Enter your own run to see its drop.

0%3%5%10%
6 mm²2.4%10 mm²1.5%16 mm²0.91%25 mm²0.58%35 mm²0.42%Drawn to scale, with each size’s drop for this run
Volts lost
3.632 V of 400 V
Heat in the wire
201.3 W
Longest run for 3%
165.2 m

Physics only: the drop for the size you picked, not a wire size for your circuit, which also depends on ampacity and your local code.

Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs. Terms

How this works: 6 sources,

How this works

Method

In a balanced three-phase circuit the return currents cancel in the neutral, and the drop between lines is √3 times the length, current and resistance per metre, instead of the 2 of a single-phase circuit. For 50 m of 16 mm² copper at 75 °C (1.31 Ω/km) carrying 32 A: 1.732 × 50 × 32 × 0.00131 = 3.63 V, 0.91% of 400 V. Full method

How it’s tested

2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.

Every change on What’s new

How we make toolsReport a mistake

How three-phase voltage drop is calculated

In a balanced three-phase circuit the return currents cancel in the neutral, and the drop between lines is √3 times the length, current and resistance per metre, instead of the 2 of a single-phase circuit. For 50 m of 16 mm² copper at 75 °C (1.31 Ω/km) carrying 32 A: 1.732 × 50 × 32 × 0.00131 = 3.63 V, 0.91% of 400 V.

That √3 is why three phase moves power so efficiently: at the same current and voltage, the same conductor size carries √3 times the power of a single-phase circuit and loses less, √3 instead of 2 times L × I × R′. The heat lost is I² × R in each of the three conductors.

The calculation uses resistance only. In large cables (roughly 50 mm² or 1/0 AWG and up) the cable’s reactance adds a noticeable share at power factors below 1, so a full design uses impedance tables for the actual cable and installation. For smaller sizes the resistive result is close.

Vd(line to line) = √3 × L × I × ρ(T) ÷ A · heat = 3 × I² × L × R′

Longest 400 V three-phase run for a 3% drop

Copper at 75 °C, resistance only, at three currents. Lengths are one way.

Copper at 75 °C, resistance only, at three currents. Lengths are one way.
Size16 A32 A63 A
2.5 mm²52 m26 m13 m
4 mm²83 m41 m21 m
6 mm²124 m62 m31 m
10 mm²207 m103 m52 m
16 mm²330 m165 m84 m
25 mm²516 m258 m131 m
35 mm²723 m361 m184 m
50 mm²1033 m516 m262 m
70 mm²1446 m723 m367 m
95 mm²1962 m981 m498 m
Show all 11 rows
120 mm²2478 m1239 m629 m

Common questions

Why √3 and not 2?

In a balanced load the three currents add to zero, so there is no return current in the neutral. Measured between two lines, each line’s drop is a vector 120° from the next, and the difference of two of them is √3 times one.

Is the percentage of the line-to-line or line-to-neutral voltage?

The calculator gives the line-to-line drop as a share of the line-to-line voltage (400 V, 480 V). It is the same percentage of the line-to-neutral voltage, since both shrink by the same factor.

What about motor starting?

A motor can draw several times its running current when it starts, so the drop is several times larger for a moment. Enter the starting current to see that dip; the motor’s data sheet gives it.