Three-Phase Voltage Drop Calculator
The voltage a balanced three-phase run loses between lines…
The voltage a balanced three-phase run loses between lines, with √3 in place of the 2 of a single-phase circuit, and the heat lost in the three conductors.
From the supply to the load, not there and back.
Conductor temperature75 °C (a warm conductor near full load)
Wire warms up under load: 20 °C cool and lightly loaded; 75 °C to 90 °C near full load.
ExampleVoltage drop
0.908%
50 m of 16 mm² copper carrying 32 A on 400 V three phase loses 3.632 V, leaving 396.4 V at the load.
Enter your own run to see its drop.
- Volts lost
- 3.632 V of 400 V
- Heat in the wire
- 201.3 W
- Longest run for 3%
- 165.2 m
Physics only: the drop for the size you picked, not a wire size for your circuit, which also depends on ampacity and your local code.
Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs. Terms
How this works: 6 sources,
How this works
Method
In a balanced three-phase circuit the return currents cancel in the neutral, and the drop between lines is √3 times the length, current and resistance per metre, instead of the 2 of a single-phase circuit. For 50 m of 16 mm² copper at 75 °C (1.31 Ω/km) carrying 32 A: 1.732 × 50 × 32 × 0.00131 = 3.63 V, 0.91% of 400 V. Full method
Sources
- IEC 60364-5-52:2009+AMD1:2024, Annex G (informative): voltage drop in consumers’ installations (IEC)
- Electrical Installation Guide: maximum voltage drop limit (Schneider Electric)
- Copper Wire Tables, Handbook 100 (resistivity 0.017241 Ω·mm²/m and α 0.00393 at 20 °C; AWG tables) (National Bureau of Standards (NIST), 1966)
- Aluminum Wire Tables, Handbook 109 (EC-H19 at 61% IACS: 0.028264 Ω·mm²/m, α 0.00403) (National Bureau of Standards (NIST), 1972)
- ASTM B258, Standard nominal diameters and cross-sectional areas of AWG sizes of solid round wires (ASTM International)
- IEC 60228:2023, Conductors of insulated cables (nominal sizes 0.5 to 3,500 mm²) (IEC, 2023)
How it’s tested
2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.
How three-phase voltage drop is calculated
In a balanced three-phase circuit the return currents cancel in the neutral, and the drop between lines is √3 times the length, current and resistance per metre, instead of the 2 of a single-phase circuit. For 50 m of 16 mm² copper at 75 °C (1.31 Ω/km) carrying 32 A: 1.732 × 50 × 32 × 0.00131 = 3.63 V, 0.91% of 400 V.
That √3 is why three phase moves power so efficiently: at the same current and voltage, the same conductor size carries √3 times the power of a single-phase circuit and loses less, √3 instead of 2 times L × I × R′. The heat lost is I² × R in each of the three conductors.
The calculation uses resistance only. In large cables (roughly 50 mm² or 1/0 AWG and up) the cable’s reactance adds a noticeable share at power factors below 1, so a full design uses impedance tables for the actual cable and installation. For smaller sizes the resistive result is close.
Vd(line to line) = √3 × L × I × ρ(T) ÷ A · heat = 3 × I² × L × R′
- IEC 60364-5-52’s informative Annex G gives 3% for lighting and 5% for other uses as the voltage drop limits for installations supplied from a public low-voltage network. Source: IEC 60364-5-52:2009+AMD1:2024, Annex G (informative): voltage drop in consumers’ installations.
- Schneider Electric’s installation guide explains the same limits and the higher ones (6% and 8%) for installations with their own transformer. Source: Electrical Installation Guide: maximum voltage drop limit.
Longest 400 V three-phase run for a 3% drop
Copper at 75 °C, resistance only, at three currents. Lengths are one way.
| Size | 16 A | 32 A | 63 A |
|---|---|---|---|
| 2.5 mm² | 52 m | 26 m | 13 m |
| 4 mm² | 83 m | 41 m | 21 m |
| 6 mm² | 124 m | 62 m | 31 m |
| 10 mm² | 207 m | 103 m | 52 m |
| 16 mm² | 330 m | 165 m | 84 m |
| 25 mm² | 516 m | 258 m | 131 m |
| 35 mm² | 723 m | 361 m | 184 m |
| 50 mm² | 1033 m | 516 m | 262 m |
| 70 mm² | 1446 m | 723 m | 367 m |
| 95 mm² | 1962 m | 981 m | 498 m |
Show all 11 rowsShow fewer
| 120 mm² | 2478 m | 1239 m | 629 m |
Common questions
Why √3 and not 2?
In a balanced load the three currents add to zero, so there is no return current in the neutral. Measured between two lines, each line’s drop is a vector 120° from the next, and the difference of two of them is √3 times one.
Is the percentage of the line-to-line or line-to-neutral voltage?
The calculator gives the line-to-line drop as a share of the line-to-line voltage (400 V, 480 V). It is the same percentage of the line-to-neutral voltage, since both shrink by the same factor.
What about motor starting?
A motor can draw several times its running current when it starts, so the drop is several times larger for a moment. Enter the starting current to see that dip; the motor’s data sheet gives it.