DC Voltage Drop Calculator (12 V, 24 V, 48 V)

How many volts a battery or solar cable loses over its run…

How many volts a battery or solar cable loses over its run, and how much power turns to heat. At 12 V a few tenths of a volt is a big share.

V
Common

From the supply to the load, not there and back.

Wire size
Conductor temperature75 °C (a warm conductor near full load)
°C
Common

Wire warms up under load: 20 °C cool and lightly loaded; 75 °C to 90 °C near full load.

ExampleVoltage drop

8.74%

5 m of 4 mm² copper carrying 20 A on 12 V DC loses 1.048 V, leaving 10.95 V at the load.

Enter your own run to see its drop.

0%3%5%15%
1.5 mm²23%2.5 mm²14%4 mm²8.7%6 mm²5.8%10 mm²3.5%Drawn to scale, with each size’s drop for this run
Volts lost
1.048 V of 12 V
Heat in the wire
20.97 W
Longest run for 3%
1.717 m

Physics only: the drop for the size you picked, not a wire size for your circuit, which also depends on ampacity and your local code.

Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs. Terms

How this works: 6 sources,

How this works

Method

The current flows out on one wire and back on the other, so a DC run of 5 m has 10 m of conductor in the loop. Multiply that by the current and the resistance per metre: 20 A through 4 mm² copper, warm at 75 °C (0.00524 Ω per metre), loses 2 × 5 × 20 × 0.00524 = 1.05 V. On a 12 V battery that is 8.7%, and a fridge or inverter at the far end sees under 11 V. Full method

How it’s tested

2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.

Limits

Voltage drop physics only: it does not account for NEC or IEC ampacity, insulation temperature, installation method or local code, and does not tell you what wire size a circuit needs.

Privacy

On your device. Nothing you enter or open leaves this browser. About privacy labels

Changes

  • First published: voltage drop for DC, single and three phase in AWG, kcmil or mm², with wire drawn to scale, plus DC, three-phase, AWG to mm² and wire resistance pages.

Every change on What’s new

How we make toolsReport a mistake

How to work out DC voltage drop

The current flows out on one wire and back on the other, so a DC run of 5 m has 10 m of conductor in the loop. Multiply that by the current and the resistance per metre: 20 A through 4 mm² copper, warm at 75 °C (0.00524 Ω per metre), loses 2 × 5 × 20 × 0.00524 = 1.05 V. On a 12 V battery that is 8.7%, and a fridge or inverter at the far end sees under 11 V.

The same cable on a 24 V system carrying the same power needs half the current, so it loses half the volts, a quarter of the share of the voltage and a quarter of the heat. That is why larger solar, van and boat systems move to 24 V or 48 V: thinner cable for the same result.

Low-voltage loads are sensitive: inverters cut out at a low-voltage threshold, and motors and chargers work harder as the voltage falls. Battery and solar makers usually ask for a few percent at most on main cables. Keep runs short, put the battery near the big loads, and check every connection, which adds resistance too.

Vd = 2 × L × I × ρ(T) ÷ A · % = Vd ÷ V × 100 · heat = I² × 2 × L × R′

Volts lost per 5 m run at 20 A

A 5 m one-way run (10 m of copper) carrying 20 A at 75 °C, and what share of 12, 24 and 48 V that is. The loss is the same in volts whatever the system voltage.

A 5 m one-way run (10 m of copper) carrying 20 A at 75 °C, and what share of 12, 24 and 48 V that is. The loss is the same in volts whatever the system voltage.
SizeVolts lost12 V24 V48 V
1.5 mm²2.8 V23.3%11.6%5.82%
2.5 mm²1.68 V14%6.99%3.49%
12 AWG1.27 V10.6%5.28%2.64%
4 mm²1.05 V8.74%4.37%2.18%
10 AWG0.797 V6.64%3.32%1.66%
6 mm²0.699 V5.82%2.91%1.46%
8 AWG0.501 V4.18%2.09%1.04%
10 mm²0.419 V3.49%1.75%0.874%
6 AWG0.315 V2.63%1.31%0.657%
16 mm²0.262 V2.18%1.09%0.546%
Show all 14 rows
4 AWG0.198 V1.65%0.826%0.413%
25 mm²0.168 V1.4%0.699%0.349%
2 AWG0.125 V1.04%0.52%0.26%
35 mm²0.12 V0.998%0.499%0.25%

Common questions

Is length one way or round trip?

Enter the one-way distance from the battery or panel to the load. The calculator doubles it for the return wire. If your positive and negative run different routes, enter the average of the two.

What drop is acceptable on a 12 V system?

Many battery, inverter and boat-wiring guides aim for about 3% on important circuits, which is only 0.36 V at 12 V. Check your equipment maker’s figure: inverters often specify cable sizes for their full current and length.

Why does my inverter shut down on a long cable?

At high current the cable loses volts, so the inverter sees a lower voltage than the battery has and trips its low-voltage cut-out. Shorter or thicker cables, or a higher system voltage, reduce the drop.

Does this tell me what cable to buy?

No. It gives the voltage drop of the size you pick. A cable must also carry the current without overheating, which depends on its insulation, how it is installed and bundled, and the rules for your vehicle, boat or building.