Battery Bank Size Calculator
How big a battery bank has to be to run what you use each day for a set number of…
How big a battery bank has to be to run what you use each day for a set number of days without sun or shore power, for lead-acid or lithium.
Each device’s watts × hours, added.
Battery type
Usable share and inverter50% used, inverter 90%
50% is Victron’s lead-acid default; 80 to 90% for lithium.
87 to 92% at best for small inverters.
ExampleBank at 12 V
444Ah
To run 1.2 kWh a day for 2 days without charging, using 50% of a lead-acid (AGM, gel) bank through a 90% inverter, you need 444 Ah at 12 V (5.33 kWh).
Enter your own daily use to size your bank.
- Your use over 2 days: 2.4 kWh
- Inverter losses: 266.7 Wh
- Kept in reserve: 2.667 kWh
- Total energy
- 5.333 kWh
- As 12 V 100 Ah batteries
- 5 in parallel
- Usable over the days
- 2.667 kWh
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician. Terms
How this works: 6 sources,
How this works
Method
Start from energy, not amps: add up what you use in a day in watt hours (each device’s watts × the hours it runs). A fridge averaging 50 W all day is 1,200 Wh. Multiply by the days the bank must last without charging, then allow for the losses and the share of the battery you can use. Full method
Sources
- BMV-700 manual: discharge floor (50% lead-acid, 10 to 20% lithium) (Victron Energy)
- Phoenix Inverter VE.Direct 250 to 1200 VA datasheet (max. efficiency 87 to 92%, zero-load power 4.2 to 12 W) (Victron Energy)
- BMV-700 manual: battery capacity and Peukert exponent (1.25 default) (Victron Energy)
- Peukert’s law (Wikipedia)
- 12.8 V and 25.6 V Lithium SuperPack datasheet (2,500 cycles at 80% DoD) (Victron Energy)
- PackSafe: lithium batteries (100 Wh and 160 Wh limits) (US Federal Aviation Administration)
How it’s tested
2 worked examples for this page are checked by automated tests before every release: given the inputs, the tool must show the expected answer.
Limits
Circuit physics for learning and planning, not wiring advice: installations must follow your local electrical code and a qualified electrician.
Privacy
On your device. Nothing you enter or open leaves this browser. About privacy labels
Changes
- First published: battery runtime with depth of discharge, inverter losses and idle draw, and Peukert’s law, plus Ah to Wh, mAh to Wh with flight limits, and battery bank size pages.
How to size a battery bank
Start from energy, not amps: add up what you use in a day in watt hours (each device’s watts × the hours it runs). A fridge averaging 50 W all day is 1,200 Wh. Multiply by the days the bank must last without charging, then allow for the losses and the share of the battery you can use.
An inverter wastes part of what it draws, so divide by its efficiency: 2,400 Wh over two days becomes 2,667 Wh at 90%. Then divide by the usable share. Lead-acid batteries last much longer if they are not run below about half, so a lead-acid bank needs twice its usable energy: 5,333 Wh, or 444 Ah at 12 V. Lithium iron phosphate can use 80% or more, so the same job needs 3,333 Wh, 260 Ah at 12.8 V.
Larger banks are easier at higher voltages: 444 Ah at 12 V is 111 Ah at 48 V, with a quarter of the current and much thinner cables. Add a margin for cold weather, ageing and cloudy days; solar charging is sized separately.
Bank Wh = daily Wh × days ÷ (inverter efficiency × usable share) · Ah = Wh ÷ V
- Victron’s battery monitor sets the discharge floor at 50% for lead-acid by default, and suggests 10 to 20% for lithium. Source: BMV-700 manual: discharge floor (50% lead-acid, 10 to 20% lithium).
- Victron’s Phoenix inverters (250 to 1,200 VA) peak at 87 to 92% efficiency and draw 4 to 12 W with no load. Source: Phoenix Inverter VE.Direct 250 to 1200 VA datasheet (max. efficiency 87 to 92%, zero-load power 4.2 to 12 W).
Bank sizes for two days without charging
Ah needed for each daily use over 2 days, through a 90% inverter: lithium at 80% use, lead-acid at 50%.
| Daily use | Lithium, 12.8 V | Lead-acid, 12 V | Lithium, 51.2 V | Lead-acid, 48 V |
|---|---|---|---|---|
| 300 Wh | 65.1 Ah | 111 Ah | 16.3 Ah | 27.8 Ah |
| 500 Wh | 109 Ah | 185 Ah | 27.1 Ah | 46.3 Ah |
| 1,000 Wh | 217 Ah | 370 Ah | 54.3 Ah | 92.6 Ah |
| 1,500 Wh | 326 Ah | 556 Ah | 81.4 Ah | 139 Ah |
| 2,000 Wh | 434 Ah | 741 Ah | 109 Ah | 185 Ah |
| 3,000 Wh | 651 Ah | 1,110 Ah | 163 Ah | 278 Ah |
| 4,000 Wh | 868 Ah | 1,480 Ah | 217 Ah | 370 Ah |
| 5,000 Wh | 1,090 Ah | 1,850 Ah | 271 Ah | 463 Ah |
| 8,000 Wh | 1,740 Ah | 2,960 Ah | 434 Ah | 741 Ah |
| 10,000 Wh | 2,170 Ah | 3,700 Ah | 543 Ah | 926 Ah |
Common questions
How many days of autonomy do I need?
Enough to cover the longest stretch without charging that you want to ride out: fewer days when a generator or the grid is there as a backup, more for an off-grid site in a cloudy climate. Each extra day adds a full day’s energy to the bank.
Why does lead-acid need a bigger bank?
Using only about half of a lead-acid battery keeps it from wearing out quickly, so you buy twice the capacity you use. Lithium iron phosphate is rated for thousands of cycles at 80% use (2,500 in Victron’s datasheet), so the bank can be smaller for the same job.
Does this size the solar panels too?
No. The panels have to put back each day’s use plus losses, which depends on your sun hours by place and season. Size the bank here, then the array from your location’s solar data.